Wskaźniki napięcia
The AOUF-1/1 acoustic visual phase comparator is used for phasing in nets and alternating current devices 50 Hz and rated voltage from 0.23 kV up to 1.2 kV. It works in conjunction with UDI-B universal insulating pole with appropriate rating voltage. The producer recommends the UDI-B insulating poles filled with insulating foam.
It is equipped with cylindrical housing made of black color plastic, resistant for bridging. It is also drop-resistant and impact-resistant according to EN 61481:2001+A/C standard. Its design assures splash-proofing.
The AOUF-1/2 acoustic visual phase comparator is used for phasing in nets and alternating current devices 50 Hz and rated voltage from 3 kV up to 36 kV. It works in conjunction with UDI universal insulating pole with appropriate rating voltage.
The AOWN-5 sound-optical voltage detector is designed for acoustic and optical signalling of the presence of alternating voltage in 50 Hz networks with the rated voltage from 0.23 kV up to 400 kV. It works in conjunction with the UDI-B universal insulating pole designed for appropriate rated voltage.
The C.A. 704 is low-voltage of direct and alternating current digital sound-optical detector, circuit continuity detector and phase swirl direction detector (two-conductor’s method).
The C.A. 760 is low-voltage of direct and alternating current digital sound-optical detector of diode type, circuit continuity detector and phase swirl direction detector (two-conductor’s method). C.A.
The CHM ultrasonic height meter is designed to measurement power network conductor’s hanging in three-conductors configuration of the CHM300 type or six-conductors configuration of the CHM600 type. It works on principle of measurement the deceleration time between the moments of wave dispatching and reflection from a measured object. Maximum conductors hanging height is 23 m (for E model). To compensate environment temperature influence on propagation speed of waves, the instrument has been equipped with temperature sensor. It enables to automatically compensate temperature influence.
The DPPE-1 is detector of alternate electrical field which is designed to detect presence of AC electrical field without contact betveen detector and field source (electrcal devices and installations). Indication is sound-optcal signal, characteristic of detection is directional. Detectors are designed to work with fields around devices under voltage of 0.23 kV - 400 kV range and frequency of 50Hz/60Hz. Detector operates within the following rated voltage ranges:
0.23 kV – 400 kV - DPPE-1
1 kV – 30 kV - DPPE-1/A
30 kV – 400 kV - DPPE-1/B
The DUSPOL is a diode low-voltage acoustic-visual direct/alternating current circuit continuity detector and phase swirl direction detector (two-conductor’s method).
The detector’s design meets the requirements of the standards: PN-EN 61243-3:2002 and DIN VDE 0682-0401.
The advantages are as follows:
- high level of electrical safety, automatic signalling AC/DC protects user from mistaken interpretation,
- auto-test enables to check the internal electronic circuits and measuring conductors’ condition,
- vibration alarm for voltage detection,
- lighting of work location,
DWNP-1 two pole A.C. voltage detector is designed for checking presence of voltage in range 10V - 1000V; it has LED display nad indicats level of voltage with 5V step. Detector works in conjunction with TDO-4-B, TDI and TDI/I or UDI-B; device consist of two parts:
• resistance part, equipped with the contact pin fastened in the pole head,
• measuring part, equipped with digital display and magnetic earth clamp,
connected with a wire with silicon insulation.